title: "PPS Educational Adequacy and Facility Assessment: School Deficiency Listing, Irvington K-8 School (Magellan Consulting, printed 2/8/2008)"
url: "https://www.pps.net/cms/lib/OR01913224/Centricity/Domain/58/School%20Deficiency%20Listing/Irvington_rev.pdf"
archived_copy: "https://web.archive.org/web/20170903104244/https://www.pps.net/cms/lib/OR01913224/Centricity/Domain/58/School%20Deficiency%20Listing/Irvington_rev.pdf"
retrieved: "2026-10-26"
source_type: "PPS facility assessment database printout (3-page PDF). Original URL returns 404; text from the Internet Archive copy captured 2017-09-03."
publisher: "Portland Public Schools / Magellan Consulting (A.P.P.L.E.)"
note: "Irvington, Building A: 'Elevator Is Missing And Needed' (Priority 1, Conveyances); 'Elevation changes prevent access' (three Priority 1 entries); 'Completely nonaccessible toilet room' (Priority 1); inaccessible drinking fountains."
---

# PPS Educational Adequacy and Facility Assessment: School Deficiency Listing, Irvington K-8 School (Magellan Consulting, printed 2/8/2008)

Unofficial text extraction (poppler pdftotext -layout) for research; may contain extraction errors. Consult the original.

```
PPS Educational Adequacy and Facility Assessment                                                                          School Deficiency Listing
                                                                                                                                               2/8/2008 2:21 PM
          259               Irvington K-8 School


School and Site Level Deficiencies
Site
Deficiency                                                                                                          ID         Qty UoM         Priority
Concrete Walks Are Damaged And Require Replacement                                                                6008        2,000 SF            3

Asphalt Paving Is Damaged And Requires Replacement                                                                6007          56 CAR            4

Surface missing or not compliant.                                                                                11774           4 Ea.            4

Bollards Are Damaged And Require Replacement                                                                      6010           7 Ea.            5

Bus drop-off area does not have a canopy.                                                                        14007         100 LF             5

K playground not appropriately fenced or buffered.                                                               14045           1 Ea.            5

Play Field Requires Regrading                                                                                     6011        1,800 SF Surf       5

School lacks marquee or marquee in poor condition.                                                               13873           1 Ea.            5

Small Benches Are Damaged And Require Replacement                                                                 6009           2 Ea.            5

                                                                                                  Sub Total for System           9

Electrical
Deficiency                                                                                                          ID         Qty UoM         Priority
The Pole Lighting Is Damaged And Should Be Replaced                                                               6032           7 Ea.            3

                                                                                                  Sub Total for System           1

Technology
Deficiency                                                                                                          ID         Qty UoM         Priority
Facility lacks centralized video distribution equipment                                                          16739           1 Ea.            3

Facility lacks VOIP central equipment                                                                            16828           1 Ea.            3

                                                                                                  Sub Total for System           2
                                                                                    Sub Total for School and Site Level         12

Building: A - Main Building
Site
Deficiency                                                                                                          ID         Qty UoM         Priority
Elevation changes prevent access (curbs, stairs, stages, doorway thresholds etc.)                                12035           1 LF             1

                                                                                                  Sub Total for System           1

Exterior
Deficiency                                                                                                          ID         Qty UoM         Priority
The Metal Exterior Door Is Damaged And Requires Replacement                                                       6013           8 Door           2

The Wood Exterior Door Is Damaged And Requires Replacement                                                        6012           1 Door           2

The Wood Window Is Damaged And Requires Replacement                                                               6014          25 Ea.            2

Exterior Doors is not equipped with Card Key Access                                                              17809          17 Ea.            3

                                                                                                  Sub Total for System           4

Interior
Deficiency                                                                                                          ID         Qty UoM         Priority
Acoustical Wall Treatment is missing and is needed                                                               14757        3,144 SF            3

Door is not equiped with Card Key Access                                                                         17647         108 Ea.            3

The Carpet Flooring Is Damaged And Requires Replacement                                                           6016        2,500 SF            3

The Ceramic Tile Flooring Is Damaged And Requires Replacement                                                     6019        3,500 SF            3

The Vinyl Composition Tile Flooring Is Damaged And Requires Replacement                                           6017       49,984 SF            3

Blinds are missing or in poor condition.                                                                         14773         390 SF Surf        4

Interior Ceramic Walls Require Repair Or Replacement                                                              6015        1,500 SF Wall       4

The Wood Flooring Is Damaged And Requires Repair                                                                  6018        3,360 SF            4

Elementary School lacks appropriate wayfinding system.                                                           14143           1 Ea.            5

Large rooms lack capacity signs.                                                                                 14774           6 Ea.            5

                                                                                                  Sub Total for System          10




                                                                                                                                  Irvington K-8 School    259
A▪P▪P▪L▪E ©, Magellan Consulting, Inc. 2007                                                                                                      Page 1 of 3
PPS Educational Adequacy and Facility Assessment                                                         School Deficiency Listing
                                                                                                                             2/8/2008 2:21 PM
          259                 Irvington K-8 School

Mechanical
Deficiency                                                                                         ID         Qty UoM        Priority
Kitchen Fire Suppression Hood is Missing                                                         6977           1 Ea.           2

Lab lacks an air exchange system.                                                               14766           1 Ea.           2

The Boiler HVAC Component Is Damaged And Requires Replacement                                    7418        8,000 MBH          2

Exhaust Fan Ventilation Is Damaged And Should Be Replaced                                        6026           4 Ea.           4

Duct Cleaning Required                                                                           6024       65,285 SF           5

Duct Grill is Damaged And Should Be Replaced                                                     6025          28 Ea.           5

                                                                                  Sub Total for System          6

Electrical
Deficiency                                                                                         ID         Qty UoM        Priority
The Exterior Electrical Enclosure Is Damaged And Should Be Repaired                              7419           4 Ea.           2

Circuits need to be added to support additional outlets                                         16639          10 Ea.           3

Lightning Protection System is Missing and Needed                                                6033       65,285 SF           3

The H.I.D. Lighting Is Damaged And Should Be Replaced                                            6035           6 Ea.           3

The Mounted Building Lighting Is Damaged And Should Be Replaced                                  6031           9 Ea.           3

The 1 X 4 Interior Fluorescent Lighting Is Damaged And Should Be Replaced                        6034          68 Ea.           4

Room does not have tamper-proof light switching.                                                14761           2 Ea.           5

Room has insufficient electrical outlets.                                                       14758         101 Ea.           5

Room lacks controls to partially dim lights.                                                    14772           4 Ea.           5

Room lighting is inadequate or in poor condition.                                               14771       12,221 SF           5

                                                                                  Sub Total for System         10

Plumbing
Deficiency                                                                                         ID         Qty UoM        Priority
Completely nonaccessible toilet room.                                                           12032           1 Ea.           1

The Toilets Plumbing Fixtures Are Damaged And Should Be Replaced                                 6029          78 Ea.           3

The Urinal Plumbing Fixtures Are Damaged And Should Be Replaced                                  6030          26 Ea.           3

Drinking Fountain unit not accessible.                                                          12036           1 Ea.           4

Drinking Fountain unit not accessible.                                                          12037           2 Ea.           4

The Class Room Lavatories Plumbing Fixtures Are Damaged And Should Be Replaced                   6028          22 Ea.           4

The Non-Refrigerated Drinking Fountain is Damaged And Should Be Replaced                         6027          12 Ea.           4

Room lacks a drinking fountain.                                                                 14769          10 Ea.           5

Room lacks private toilets.                                                                     14767           7 Ea.           5

The Class Room Lavatories Plumbing Fixtures Are Missing And Should Be Installed                 14768          20 Ea.           5

                                                                                  Sub Total for System         10

Fire and Life Safety
Deficiency                                                                                         ID         Qty UoM        Priority
Room lacks an appropriate eyewash.                                                              14770           1 Ea.           1

PA Speakers are missing or need to be replaced                                                  18954          11 Ea.           2

Building not equipped with Card Key Access Control                                              18059           1 Ea.           3

Computer room lacks independent AC.                                                             18143           1 Ea.           3

                                                                                  Sub Total for System          4

Technology
Deficiency                                                                                         ID         Qty UoM        Priority
Administrative / Support area lacks data drop(s)                                                17252          14 Ea.           3

Administrative or support area lacks VOIP phone handset                                         17446          14 Ea.           3

Building lacks enough wireless data points                                                      17090           8 Ea.           3

Classroom lacks technology upgrade                                                              14775          36 Ea.           3

Classroom lacks VOIP phone handset                                                              18450          35 Ea.           3

Room has insufficient dataports.                                                                14759         194 Ea.           5


                                                                                                                Irvington K-8 School    259
A▪P▪P▪L▪E ©, Magellan Consulting, Inc. 2007                                                                                    Page 2 of 3
PPS Educational Adequacy and Facility Assessment                                                                                   School Deficiency Listing
                                                                                                                                                        2/8/2008 2:21 PM
         259               Irvington K-8 School

Technology
Deficiency                                                                                                                   ID         Qty UoM         Priority
Room lacks telephone wiring for VOIP system.                                                                              14760           2 Ea.            5

                                                                                                           Sub Total for System           7

Conveyances
Deficiency                                                                                                                   ID         Qty UoM         Priority
Elevation changes prevent access (curbs, stairs, stages, doorway thresholds etc.)                                         12033           1 Ea.            1

Elevation changes prevent access (curbs, stairs, stages, doorway thresholds etc.)                                         12034           1 Ea.            1

Elevator Is Missing And Needed                                                                                            12023           1 Ea.            1

                                                                                                           Sub Total for System           3

Specialties
Deficiency                                                                                                                   ID         Qty UoM         Priority
The Base Storage Cabinets Require Replacement                                                                              6020         280 LF             4

The Upper Storage Cabinets Require Replacement                                                                             6021          80 LF             4

The Wardrobe Storage Cabinets Require Replacement                                                                          6022          80 LF             4

Room has insufficient tackboard area.                                                                                     14763          45 Ea.            5

Room has insufficient writing area.                                                                                       14762          77 Ea.            5

Room lacks appropriate amount of teacher storage.                                                                         14764          55 Ea.            5

Room lacks the required demonstration table.                                                                              14765           1 Ea.            5

Stage lacks necessary equipment.                                                                                          13948           1 Ea.            5

                                                                                                           Sub Total for System           8

Other
Deficiency                                                                                                                   ID         Qty UoM         Priority
Crawlspace has asbestos containing material                                                                               18326       19,320 SF            2

General hazardous materials deficiency                                                                                    13669           1 LS             2

                                                                                                           Sub Total for System           2
                                                                                        Sub Total for Building A - Main Building         65

Building: B - Covered Play Area
Exterior
Deficiency                                                                                                                   ID         Qty UoM         Priority
The Exterior Requires Cleaning                                                                                             6036        1,200 SF Wall       5

The Exterior Requires Painting                                                                                             6037        1,200 SF Wall       5

The Exterior Soffit Is Damaged And Requires Repair                                                                         6038        1,200 SF            5

                                                                                                           Sub Total for System           3

Interior
Deficiency                                                                                                                   ID         Qty UoM         Priority
The Exposed Ceilings Are Damaged And Requires Repainting                                                                   6039        4,900 SF            5

                                                                                                           Sub Total for System           1

Electrical
Deficiency                                                                                                                   ID         Qty UoM         Priority
Lightning Protection System is Missing and Needed                                                                          6040        4,900 SF            3

                                                                                                           Sub Total for System           1

Fire and Life Safety
Deficiency                                                                                                                   ID         Qty UoM         Priority
PA Speakers are missing or need to be replaced                                                                            18953           1 Ea.            2

                                                                                                           Sub Total for System           1
                                                                                    Sub Total for Building B - Covered Play Area          6
                                                                                                              Total for Campus           83




                                                                                                                                           Irvington K-8 School    259
A▪P▪P▪L▪E ©, Magellan Consulting, Inc. 2007                                                                                                               Page 3 of 3
```